Gas Extinguishing Standard - Part 7: Commissioning and acceptance

December 2001 Fire & Safety

Part 1: May 2001


Part 2: June 2001


Part 3: July 2001


Part 4: September 2001


Part 5: October 2001


Part 6: November 2001


The completed system shall be reviewed and tested by qualified personnel to meet the approval of the authority. Only equipment and devices designed to national standards shall be used in the system. To determine that the system has been properly installed and will function as specified, the following tests shall be performed.

Enclosure check

Determine that the protected enclosure is in general conformance with the plans.

Review of mechanical components

The piping distribution system shall be inspected to determine that it is in compliance with the design and installation documents. Nozzles and pipe size and, if appropriate, pressure-reducing devices, shall be in accordance with system drawings. The means of pipe size reduction and attitudes of tees shall be checked for conformance to the design. Piping joints, discharge nozzles and piping supports shall be securely fastened to prevent unacceptable vertical or lateral movement during discharge. Discharge nozzles shall be installed in such a manner that piping cannot become detached during discharge.

During assembly, the piping distribution systems shall be inspected internally to detect the possibility of any oil or particulate matter which could soil the hazard area or affect the extinguishant distribution due to a reduction in the effective nozzle orifice area.

The discharge nozzles shall be oriented in such a manner that optimum extinguishant dispersal can be effected. If nozzle deflectors are installed, they shall be positioned to obtain the maximum benefit.

The discharge nozzles, piping, and mounting brackets shall be installed in such a manner that they will not potentially cause injury to personnel. Extinguishant shall not directly impinge on areas where personnel may be found in the normal work area or on any loose objects or shelves, cabinet tops or similar surfaces where loose objects could be present and become missiles.

All extinguishant storage containers shall be properly located in accordance with 'approved for construction' set of system drawings. All containers and mounting brackets shall be securely fastened in accordance with the manufacturer's requirements.

A discharge test for extinguishants is generally not recommended. However, if a discharge test is to be conducted, the mass of extinguishant shall be determined by weighing or other approved methods. Concentration measurements should be made at a minimum of three points, one at the highest hazard level.

Other assessment methods may normally be used to reduce necessary discharge into the environment, for example, the door fan pressurisation test. However, a discharge test may be conducted if acceptable to the authority.

An adequate quantity of extinguishant to produce the desired specified concentration shall be provided. The actual enclosure volumes shall be checked against those indicated on the system drawings to ensure the proper quantity of extinguishant. Fan rundown and damper closure time shall be taken into consideration.

Unless the total piping contains not more than one change in direction fitting between the storage container and the discharge nozzle, and unless all piping has been physically checked for tightness, the following tests shall be carried out.

1. All open-ended piping shall be pneumatically tested in a closed circuit for a period of 10 min at 3 bar. At the end of 10 min, the pressure drop shall not exceed 20% of the test pressure.

2. All closed-section pipework shall be hydrostatically tested to a minimum of 1,5 times the maximum working pressure for 2 min during which there shall be no leakage. On completion of the test, the pipework shall be purged to remove moisture.

It is recommended that hydrostatic testing be carried out at the manufacturer's works where practicable.

It is important to note that pneumatic pressure testing creates a potential risk injury to personnel in the area, as a result of airborne projectiles if rupture of the piping system occurs. Prior to conducting the pneumatic pressure test, the protected area shall be evacuated and appropriate safeguards shall be provided for test personnel.

A test using nitrogen, or a suitable alternative, shall be performed on the piping network to verify that flow is continuous and that the piping and nozzles are unobstructed.

To be continued in the next issue.

For further details contact the FDIA on tel: (011) 397 1618.





Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

Standards for fire detection
SAQCC (Fire) Fire & Safety Associations
In the second article from SAQCC, Nick Collins focuses on SANS 10139, which is generally regarded as the ‘Book of Knowledge’ for any fire detection installer, commissioner and designer.

Read more...
The unusual chemistry of lithium-ion battery fires
SafeQuip Fire & Safety
Traditional fire extinguishers, which use agents like water, foam, or dry chemicals, may not be suitable for lithium-ion battery fires due to the unique challenges posed by the high-energy density of these batteries.

Read more...
Saving lives with fire safety technology
Fire & Safety News & Events
The fire protection landscape is evolving swiftly, fuelled by technological advancements designed to improve safety and efficiency in fire detection, control, and suppression. These innovations transform traditional methods and establish new safety standards in residential and commercial spaces.

Read more...
Standards for fire detection
SAQCC (Fire) Fire & Safety
In the second article from SAQCC, Nick Collins focuses on SANS 10139, which is generally regarded as the “Book of Knowledge” for any fire detection installer, commissioner and designer.

Read more...
Rational design is not just a tick-box exercise
Fire & Safety
Rational design is about achieving performance-driven fire safety measures through sound engineering principles. It is not just a tick-box exercise, but involves a deep understanding of fire risks and behaviour, and developing customised fire protection strategies.

Read more...
Fire detection and gas suppression systems
Masc Solutions Products & Solutions Fire & Safety
Masc Solutions is an official Fike distributor and installer in South Africa, providing comprehensive design, supply, and installation services for specialised gas fire suppression systems.

Read more...
New fire blanket for lithium-ion battery fires
Fire & Safety Products & Solutions
SafeQuip launched its newly developed range of high-performance, multi-use lithium-ion battery fire blankets, specifically designed to address fires involving devices with lithium-ion batteries, providing a crucial tool for safety in environments where these batteries are in use.

Read more...
SafeQuip launches lithium-ion battery fire extinguishers
Fire & Safety Products & Solutions
[Sponsored] SafeQuip has launched the SANS 1910-2022 approved Lith-Ex fire extinguisher range, which carries NTA 8133:2021 (KIWA/POOO55865) test approval, which proves its lithium-ion battery fire extinguishing capability.

Read more...
Partnership addresses fire hazard mitigation
Brigit Fire (a Division of Hudaco Trading) Elvey Security Technologies Fire & Safety Security Services & Risk Management
Brigit Fire has partnered with the Elvey Group. The collaboration will see Brigit Fire distributing both the advanced C-TEC addressable fire detection systems (CAST Technology) and GreenMist lithium extinguishers.

Read more...
Fire alarm control panel with printer
Dahua Technology South Africa Products & Solutions Fire & Safety
Dahua’s fire alarm control panel with a printer is designed to provide early warning fire detection, display fire information and offer flexibility in design and operation to meet the demands of various projects.

Read more...