Commissioning of a fire detection system

April 2017 Associations, Fire & Safety

When an installation has been completed by a competent installer, the next step is commissioning. The installer will have carried out the installation from a design specification.

Commissioning is a systematic process with documentation that extends from design through installation, testing, and training. SANS 10139:2012 part 11 gives guidance and recommendations on the commissioning and handover process.

The commissioning process ensures that the system is set to function as intended and there are no major issues that will cause false alarms. The commissioner also sees to it that the installation is of an acceptable standard.

The person responsible for commissioning a fire alarm system in accordance with the recommendations of the SANS 10139:2012 standard should possess, at least, a basic knowledge and understand design, limitation of false alarms and installation of fire detection systems. The commissioner will be disadvantaged and not be able to carry out the commissioning exercise correctly if knowledge lacks in any these disciplines. The commissioner should also have access to the requirements of the designer and any other relevant documentation or drawings that have been processed for the job.

At commissioning, the entire system should be inspected and tested to ensure that it operates satisfactorily. Below is a summary of SANS 10139:2012 Part 11. These are the minimum points, depending on the requirements and design of the system, that a commissioner should be checking:

1. All manual call points and automatic fire detectors function correctly in accordance with the recommendations in SANS 10139:2012 Part 12.

2. Every manual call point and automatic fire detector, on operation, results in the correct zone indication, and, in the case of addressable systems, correct text display, at all indicating equipment.

3. Where an optical beam detector uses a combined transmitter/receiver unit in conjunction with a reflector, care should be taken to minimise the effect of reflections (e.g. from surfaces close to the transmitter/receiver unit) from dominating the received signal. Unless the equipment has specific features to compensate for such effects, at commissioning, the installed unit should be tested by partial obscuration of the beam near to the reflector.

4. Sound pressure levels throughout all areas of the building comply with the recommendations SANS 10139:2012 Part 8 (i.e. 65db) and, where appropriate for voice alarms, an acceptable level of intelligibility is achieved in accordance with SANS 7240-16 or SANS 7240-19 throughout all areas of the building.

5. Any facility for remote transmission of fire alarm signals (and, where appropriate, fault signals) to an alarm-receiving centre operate correctly.

6. Any ‘cause and effect’ requirements of the designer (e.g. in respect of staged alarms or initiation of operation of other fire protection systems and equipment, and safety measures) are fully satisfied.

7. All alarm, control, indicating, printing, and ancillary functions of the system operate correctly and are adequately labelled or identified.

8. No changes to the building since the time of original design have compromised the compliance of the system with this standard.

9. Siting of any detection device complies with, at least, the recommendations of that device as per SANS 10139:2012 requirement.

10.A suitable and accurate zone plan is displayed in close location to the fire panel.

11. Compliance with the provision of any visual alarms, i.e. in areas where persons with disabilities may be, or areas where the ambient noise levels exceed 90db.

12. Compliance with mains power supply (fed from a dedicated circuit breaker and labelled correctly).

13. Standby power supply and calculations to determine battery capacity are provided and correct battery size installed.

14. Correct cabling has been used.

15. There is no obvious shortcoming with the stated category.

16. In radio-linked systems, radio signal strengths are adequate throughout all areas of the protected premises to ensure reliable operation of the system.

17. Adequate records of insulation resistance, earth continuity and, where appropriate, earth loop impedance tests exist.

18. All fault indicators and their circuits should be checked, where practicable, by simulation of faults conditions.

19. All relevant documentation has been provided to the user or purchaser. The documentation should include an operation and maintenance manual, drawings of the system, certificates of design, installation and commissioning and a panel print-out of all devices.

20. An FDIA log book has been supplied and installed next to the fire panel for the client to keep a running account of the system performance.

21. Labels, visible when batteries are in their normal position, should be fixed to batteries, indicating the date of installation.

The client shall be satisfied that the commissioner has provided sufficient training to all staff members in the vicinity of the fire panel on the operation and controls for the system.

On completion of the commissioning process, a certificate signed by a competent person should be issued. The measure of competency is provided by SAQCC Fire. Ensure your commissioning engineer carries his approved person card and is listed at the level of commissioner. The organisation responsible for commissioning the system might, or might not, be the same organisation that designed and/or installed the system, but the responsibility for commissioning needs to be clearly defined prior to the start of the installation work.

This signed certificate verifies the installed system operates correctly in accordance with requirements laid down by the designer, and that the commissioner carries liability for the correct operation of the system.

By utilising FDIA-registered companies you can rest easy knowing the system will be installed and commissioned correctly and the contracting staff used on site have proven to be competent persons.

For more information contact the FDIA at [email protected] or www.fdia.co.za.



Credit(s)




Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

Addressable smoke detector
Dahua Technology South Africa Products & Solutions Fire & Safety
Dahua’s addressable smoke detector connects to the addressable fire alarm control panel and analyses ambient smoke concentration through an intelligent algorithm to trigger alarms.

Read more...
Fire alarm control panel with printer
Dahua Technology South Africa Products & Solutions Fire & Safety
Dahua’s fire alarm control panel with a printer is designed to provide early warning fire detection, display fire information and offer flexibility in design and operation to meet the demands of various projects.

Read more...
Standalone smoke alarm
Dahua Technology South Africa Products & Solutions Fire & Safety
The Dahua DHI-HY-SA40A is a standalone smoke alarm that continuously monitors smoke concentration. This device works without a panel and is cost-effective and suitable for home use.

Read more...
Gas detection for mining
FS Systems Products & Solutions Fire & Safety Mining (Industry)
Flammable gas detection is critical in safeguarding mining operations, where combustible gases pose significant risks. Early detection of these gases helps prevent fires and explosions, which can lead to devastating consequences.

Read more...
ECP1000 extinguishing control panel
G2 Fire Products & Solutions Fire & Safety
The ECP1000 is a extinguishing panel built to EN54-2, EN54-4 and EN 12094–1 standards with multiple input and outputs to facilitate the protection of a single area and the connected devices.

Read more...
TeledataOne addressable panel
G2 Fire Products & Solutions Fire & Safety
The Onemini panel provides a one-loop option ideal for smaller installations, where the TeledataOne is expandable to nine loops; both are available from G2 Fire.

Read more...
Detect fires in the early stages
Securiton Products & Solutions Fire & Safety
The SecuriSmoke range from Securiton offers various levels of coverage and power to suit every budget and application. What all the models have in common is that they can detect smoke in very small quantities.

Read more...
SecuriHeat ADW linear heat detector
Securiton Products & Solutions Fire & Safety
The SecuriHeat ADW linear heat detector uses sealed tubes positioned over the detection area, and a remotely positioned control unit detects pressure changes in the tubes brought about by changing temperature.

Read more...
Fire detection goes wireless
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
Wireless technology facilitates quicker system installations with minimal disruption, reduced impact on the building’s structure, and less reliance on complex cabling. Technoswitch has introduced two wireless fire detection ranges to its portfolio.

Read more...
High-precision aspirating smoke detectors for every requirement
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
The SecuriSmoke ASD range by Securiton offers three VdS-approved models and makes the lightning-fast detection of fires both scalable and cost-effective for any environment, be it a single facility or an area.

Read more...